Rating Pressure:   

Up to 450PSI (3.1MPa)

Flow Sensitivity:

4-10GPM (15.0-37.5L/min)

Maximum Surge:

18FPS (5.5m/s)

Contact Ratings: 

Two sets of SPDT (Form C)

10.1Amps at 125/250 VAC

2.0Amps at 24 VDC

Enclosure Rating:  

NEMA 4- suitable for indoor/outdoor use

Conduit Entrances: 

Two opening for 1/2" conduit

One open, one knock-out type

Compatible Pipe:  

Steel water pipe, schedule 10 through 40

Service Use: 

Automatic Sprinkler: NFPA-13

One or Two Family Dwelling: NFPA-13D

Residential Occupancies up to 4 stories: NFPA-13R

National Fire Alarm Code: NFPA-72